    ATTENTION !


    Before filling the water tank, the drain valve(s) must be closed! The maximal filling pressure is 5 bar!

    By opening the tank fill valve (J31), it is possible to run the sys- tem in "By-Pass mode" to prevent the system from overheating. Therefore, open the tank suction- and tank fill valves.

    Condition: No foam compound in the pump.
    N/NH Pumpenserie N/NH Pump-series

    Наполнение водного резервуара


    Filling the Water Tank




    S35

    S35
    H15 H11

    H15 H11

    наполнениерезервуарадляводыспомощьюсистемыавтоматического контроля уровня воды.

    • Присоединитешлангиподачиксоединительнойчастиемкости для воды.

    • Медленно откройте гидрант.

    • Откройтеклапанынаполнениярезервуара:переведитевыключатель (S36) в позицию ”1”.

    Осуществляетсяследующий цикл:

    +Еслирезервуарнаполненменеечемна70%,откроютсянаполнительныеклапаны.

    +Загоритсяконтрольнаялампа(Н15),когдаклапанынаполнениябудут открыты.

    +Вкачествеальтернативы,контрольнаяпанельможетбытьоборудованаконтрольнойлампой(Н11),котораязагорается,когдарезервуарнаполнен менее чем на 1/4*

    +Когдарезервуарнаполнен(95%),системаавтоматическогоконтроля уровня водызакроетнаполнительныеклапаны.

    +Когдауровеньнаполнениярезервуараопускаетсяниже70%,наполнительныеклапаныоткроютсяавтоматически

    резервуар для воды опять наполняется.

    • Чтобыполностьюнаполнитьрезервуар,удерживайтепереключатель(S35)впозиции”1+”покаводанепереполнитрезервуар.

    После процедуры наполнения, переведите переключатель (S35) в позицию ”0”.

    FillingtheWaterTankbyAutomaticTankLevelCon-trol *

    • Connect supply hoses to water tank fill connection(s).

    • Open hydrant valve slowly.

    • Open tank fill valves: Turn switch (S35) to pos. "I".

    Following cycle starts:

    + If the water tank content is less than 70%, the tank fill valves will open.

    + The pilot lamp (H15) illuminates, as long as the tank fill valves are open.

    + Alternatively, the control panel can be equipped with pilot lamp (H11), which illuminates when the water tank content is less than 1/4. *

    + If the water tank is full (95%), the automatic tank level control closes the fill valves.

    + When the tank level drops to approx. 70%, the tank fill valves will open automatically - the water tank is filled up again.

    • To fill up the tank completely, hold switch (S35) in position "I+" until water flows out of the overflow.

    • After filling procedure, turn switch (S35) back into position "0".




    S35

    Наполнениерезервуарадляводыспомощьюсистемыавтоматическогоконтроля уровня воды*
    Отсоединение подающих шлангов:

    • Закройте клапангидранта.

    • Понизьтедавлениеметодомоткрытиянаполнительныхклапанов.

    -Быстропереведитепереключатель (S35) в позицию”1+”

    • Отсоединитешлангиподачиводыискрепитевсесоединения слепым сцеплением.



    Внимание!

    Максимальноедавлениенаполнения8бар,вслучаеповышениядавления,понизьтедавлениевлиниинагнетания.

    Нужно любым способом избегать наполнения резервуара для воды под давлением, превышающим 8 бар.

    Перед присоединением шлангов подачи к гидранту, спустите воду, пока из гидранта не пойдет чистая вода.


    S35

    Fillingthe WaterTankbyAutomaticTankLevelControl*
    Uncouplingthesupplyhoses:

    • Close hydrant valve.

    • Release pressure by opening the tank fill valves: Briefly turn switch (S35) into position "I+".

    • Uncouple supply hoses and provide fill connections with blind coupling.